
 |
| |
TCS 682
METER INSTALLATION
|
|
A. PLUMBING CONFIGURATION
|
|
Meters
and piping should be installed to prevent drainage of
product from the meter when the system is not running.
One way to do this is to have the inlet and outlet of the
meter lower than the associated system plumbing (sump
position). Also, undue strain on the meter's 150# flanges
from the connecting piping must be avoided.
|
|
B. SLOW FLOODING OF SYSTEM
|
|
When a
pump is turned on and a valve opened in a new, dry system,
tremendous pressure can be built up in the piping and
forced through the meter. The high pressure air causes
the meter to operate more quickly than normal. When
product reaches the meter, there is an abrupt slowing of
the meter plungers which could cause damage to the
register, plunger, gears or other components. The recommended method of starting any
system is to flood the piping gradually. This allows
product to slowly force the air from the entire system.
|
|
C. PROTECTION OF
DEBRIS
|
|
On new
installations, care must be taken to protect the meter
from damage during start-up. Damage may result from the
passage through the meter of welding slag or spatter,
thread cuttings, rust, etc. There are several methods of
protecting meters from this material including: the
insertion of a spool (a flanged length of pipe equal in
length to the meter and any accessories attached to the
meter) in place of the meter until the system is flushed,
temporarily bypassing the plumbing around the meter, or
by installing a strainer ahead of the meter in the line.
|
|
D. CALIBRATION
|
|
The meter's
calibration must be checked (and adjusted, if necessary)
using the product being metered by the user. Generally,
any meter's accuracy is maximized by calibrating it to a
specific product and installation. The 682-15 meter exceeds
the accuracy requirements specified NIST Handbook 44,
which is plus or minus 0.2% at the factory. In the field,
NIST Handbook 44 maintenance test accuracy requirements
are plus or minus .5% on a slow test, and plus or minus 0.3%
on a fast test. In a five gallon test, 0.2% = 2.31 cubic
inches, 0.3% = 3.47 cubic inches, and 0.5% = 5.78 cubic
inches. Click here for 682
calibration instructions.
|
|
|
|